Effect of Mutual Inductance Between Bipolar Transmission Lines of UHVDC and Proposal of Countermeasure

WANG Delin,L Pengfei,RUAN Siye,LEI Xiao,WANG Huawei,MA Qiyan,MA Yulong,LU Yajun,LI Shaohua,HUANG Jinhai
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2015.17.009
2015-01-01
Abstract:The problem that a sharply power drop of the non-fault pole operating at 400 kV voltage level in very short time during the restart of the other 800 kV pole after DC line fault in Yibin-Jinhua ultra-high voltage direct current(UHVDC) project was analyzed. The control principle of voltage dependent current order limiter (VDCOL) was introduced, and the mutual inductance characteristics between bipolar transmission lines of UHVDC during the restart of one pole were analyzed with Lenz's law. A formula was derived for UHVDC bipolar line mutual inductance. The correctness of this formula was verified through the actual system simulation for Yibin-Jinhua UHVDC project. An improvement method for UHVDC control and protection system was proposed to prevent the power drop of non-fault pole during the restart of the other pole. The effectiveness of this new method has been proved based on the simulation model which is the same as the actual UHVDC system. The results are instructional and helpful for the design and maintenance of UHVDC system.