Interference Analysis and Protection of Electronic Current Transformer in DCB During No-load Closing of Transformer

Shijun BAI,Le GUO,Lincui ZENG,Daliang LIU,Guowei ZHANG,Haofeng LIU,Xiaohua WANG,Mingzhe RONG
DOI: https://doi.org/10.13296/j.1001-1609.hva.2018.08.013
2018-01-01
Abstract:Based on the phenomenon of protection malfunction caused by electronic current transformer abnormal work during the operation no-load closing of transformer in a 220 kV new-generation intelligent substation, depth analysis the cause of electronic current transformer abnormal work, and gives specific measures which by changing the electronic current transformer and collector grounding or by merging unit software filtering to improve the electronic current transformer anti-interference ability in DCB. Through this measures, the problem of disturbance appeared in the project put into operation is successfully solved.
What problem does this paper attempt to address?