Research on the Design of Measurement and Control of ResidualChlorine Based on Non-Membrane Sensor

Sheng LIU,Song SHI,Xinyue BAO,Hongwen GAO
DOI: https://doi.org/10.3969/j.issn.1004-1699.2017.08.028
2017-01-01
Abstract:In order to meet the needs of real-time monitoring and control of residual chlorine in the water,the related technology on the design of monitoring system of residual chlorine was studied,including non-membrane sensor design,structure design of flow-through cell and the design of potentiostatic circuit for three electrode sensor.Firstly,the internal structure and working principle of non-membrane chlorine sensor was introduced.Secondly,the design of the flow cell based on PVC material was discussed in order to under the constant flow rate of water,and then the potentiostatic circuit for the residual chlorine sensor was developed to ensure potential stability and control precision of counter electrode,so that the output of residual chlorine sensor was more stable.Finally,the calibration method,calibration process and operation rules of the sensor were described,and compared with the DPD method,the test results were in good agreement.The chlorine monitoring system based on non-membrane sensor,with the advantages of easy maintenance,high accuracy and no need to replace membrane and electrolyte,can be used for real-time online monitoring residual chlorine concentration of tap water,treated hospital wastewater,industrial circulating water and swimming pool water.
What problem does this paper attempt to address?