Modal Analysis of the 1200 MW Turbo-generator Stator End Windings

Lifei CHEN,Xinya WU,Xingjian DONG,Zhike PENG,Guang MENG
DOI: https://doi.org/10.3969/j.issn.1006-1355.2018.03.038
2018-01-01
Abstract:Modal analysis of the 1200 MW turbo-generator stator end windings are performed by finite element method. The composite conical ring structure of the stator is made up of orthotropic material. The equivalent stiffness between the positioning bracket and the conical ring is obtained based on the statics contact analysis. Later on, the homogenization equivalent model of the bar-colloid structure is established by optimization analysis method. The whole finite element model is formed by integrating all the components and its modal simulation result is verified by experimental modal analysis. The sensitivity of the first-order modal frequency to the material parameters and geometric parameters is provided. The key factors that influence the modals of the stator end of the turbo-generator are clearly defined, which provides guidance for the design of the stator end windings.
What problem does this paper attempt to address?