Pressure Drop of R134a and R1234ze(E) Flow Boiling in Microchannel Arrays with Single- and Double-Side Heating

Ji Wang,Jin Wang,Junming Li,Na Liu
DOI: https://doi.org/10.1016/j.ijheatmasstransfer.2020.120241
IF: 5.2
2020-01-01
International Journal of Heat and Mass Transfer
Abstract:An experimental study was carried out on two-phase pressure drop of R134a and R1234ze(E) flow boiling in glass microchannel arrays containing 50 parallel microchannels. Each channel has a hydraulic diameter of 301.6 mu m, an aspect ratio of 2.46 and a length of 50 mm. Experimental conditions, including saturation temperatures of 26.7 degrees C, 29.1 degrees C and 31.3 degrees C, and mass fluxes of 50-250 kg/(m(2) s), were taken into account. The effect of refrigerant properties, mass flux and saturation temperature on the flow boiling friction pressure drop were investigated. The two-phase friction pressure drop increases with increasing mass flux and decreasing saturation temperature. Specially, the effect of heating methods, including single-side heating and double-side heating, were experimentally evaluated. The two-phase friction pressure drop in microchannel arrays heated from both sides is higher than that with single-side heating. The experimental data was compared with two-phase friction pressure drop empirical correlations in the literature. The correlation provided by Zhang and Webb gives the best prediction of the experimental data with an average deviation of 34.27% for R134a and 16.88% for R1234ze(E). A new empirical correlation was provided based on the current experimental data, which could predict the current data with 94.5% prediction errors lower than 20%. (C) 2020 Elsevier Ltd. All rights reserved.
What problem does this paper attempt to address?