CFD simulation and optimization of ventilation for subway island-platform in north cities

Dong Shu-yun,You Shi-jun,Niu Run-ping,Zheng Xue-jing
DOI: https://doi.org/10.1007/s11771-007-0404-6
2007-01-01
Journal of Central South University of Technology
Abstract:To obtain the velocity and temperature field of subway station and the optimized ventilation mode, three-dimensional models of the existed station were built to evaluate and optimize the ventilation for subway island-platform station. Computational fluid dynamics (CFD) simulation was made to subway island-platform station with the boundary conditions collected for simulation computation through field measurement. The air conditioning (A/C) cooling load and ventilation energy consumption of the two kinds of subway stations were predicted with the EnergyPlus program. Because electricity consumption by ventilation equipment increases notably when PSD are used, particularly the electricity consumption by the under platform exhaust (UPE) fan, ultimately, little difference exists in the overall energy consumption with and without PSD. The PBD system is economical for the subway stations of the north cities. But PSD can prevent the air pollution and noise from the tunnel. The designers should choose a proper system according the users' request.
What problem does this paper attempt to address?