Research on Airflow and Energy Performance in PBD, PSD and PBD-PSD-combined Environment Control Systems in Subway

Yue Zhang,Xiaofeng Li
DOI: https://doi.org/10.1016/j.scs.2018.04.032
IF: 11.7
2018-01-01
Sustainable Cities and Society
Abstract:Environment control systems (ECSs) provides a comfortable environment for the passengers in subway stations, which are classified as platform bailout door (PBD), platform screen door (PSD) and PBD-PSD-combined systems. In this paper, the airflow characteristics and the energy consumption of these ECSs in typical subway stations were studied. Airflow was analyzed by a network simulation method, and the simulation results were verified by field tests. In addition, based on the cooling load calculation and the proposed operation strategy, the equipment opening time and the energy consumption of the three ECSs were analyzed in different climate zones with different operation phases. The results reveal that the PBD-PSD-combined system achieves the best energy performance among the three ECSs; however, the energy saving percentage varies in different situations. Compared to the sub-optimal ECS, the energy saving percentage of the combined system differs from 1% to 8%, while it is only 1% in hot climate zones with high passenger flow.
What problem does this paper attempt to address?