An analytical method for calculating the surface magnetic field for three-core electrical power cables

Shisong LI,Yanling YUAN,Jie DONG,Jingfu GAN,Songling HUANG,Wei ZHAO
DOI: https://doi.org/10.11857/j.issn.1674-5124.2017.04.020
2017-01-01
Abstract:Since the sum currents of three phases in the three-core cable is zero in steady state, traditional inductive current measurement methods, a current transformer, cannot measure the phase current. In order to solve this problem, this paper developed an analytical method for calculating the magnetic field on the surface of a three-core cable based on Maxwell equations which can be used for the generalized core contribution case rather than a symmetrical condition. Based on this analytical method, the phase current of the three-core cable can be represented by measurements of the magnetic field on the cable surface. The finite element simulations show that the presented analytical method has a good accuracy, and can be employed in future to realize an online power cable monitoring system.
What problem does this paper attempt to address?