A three-core power cable online monitoring system based on phase current sensing

Yanling Yuan,Jie Dong,Jingfu Gan,Shisong Li,Wei Zhao,Songling Huang,Lei Chen
DOI: https://doi.org/10.1109/I2MTC.2017.7969689
2017-01-01
Abstract:The three-core power cable shares one single shielding with three phase cores. Since it requires a lower voltage insulation and is generally less expensive, the three-core power cable has been widely used in the electrical energy transmission project below 35kV. A known problem for sensing the current of a three-core power cable is that in steady state the total current of three phases is zero, and therefore traditional inductive current measurement methods will be invalid. To solve this problem, this paper presents a magnetic sensor array for phase current measurement of a three-core power cable. In a simplest approach, three magnetic sensors, installed on the power cable surface and aligned to three phase cores of the power cable, can have a linear magnetic response of the phase current. Based on this phase current measurement technique, a three-core power cable online monitoring system is proposed for improving the reliability of a power cable system.
What problem does this paper attempt to address?