RESEARCH ON BRITTLE FRACTURE OF FRP RODS AND THE TEST METHOD

梁曦东,王成胜,范炬
DOI: https://doi.org/10.3321/j.issn:1000-3673.2003.01.009
2003-01-01
Abstract:The number of composite insulators used in China is increasing rapidly. Along with the increment of the time in service of the composite insulators the more and more failures of the composite insulators appear, in which there are many cases of the faults caused by the brittle fracture of Fiber Reinforced Plastic (FRP) rods, so the attention to this problem is widely attracted at home. In laboratory, there are two load-applying methods used to simulate the brittle fracture process, one is constant tensile load method which is used to test the resistance of FRP core against stress corrosion; the other is decreasing tensile load method, in order to simulate similar appearance of brittle fracture section in service. Now the appearance of brittle fracture of FRP rod simulated in laboratory is almost the same as that in service. The brittle fracture property of FRP rod is partly realized. Some important factors, which influence the brittle fracture process and are not well described in abroad test drafts, are discussed and clarified here. Through the study of testing conditions the test method against stress corrosion of FRP rods is given.
What problem does this paper attempt to address?