Fault Location Algorithm for Distribution Power Network Based on Relationship in Time Difference of Arrival of Traveling Wave

LIU Xiaoqin,WANG Dazhi,JIANG Xuechen,NING Yi
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.161011
2017-01-01
Abstract:Existing fault location technologies were known to perform poorly on distribution power network.In this paper,a new fault location algorithm for distribution power network based on relationship in time difference of arrival of traveling wave was demonstrated.The distribution power network was split up into several nodes giving equal interval,on the basis of these nodes,the traveling wave path matrix was constructed which represented the distances between each node and any line terminal in the network.From path matrix,it was possible to determine the propagation times of traveling wave in each path,then the matrixes of the time difference of arrival among the traveling wave of every branch for all nodes were established.When a fault occurred,the arrival times of the first fault-induced traveling waves which were monitored at the line terminals in the network were acquired by wavelet transformation.Based on the actual arrival times,the matrix of the time difference of arrival for fault point was established.Respectively,comparing the matrix for fault point with the matrix for each node,when the different was minimized between the two,the node was identified as fault point.To improve the efficiency for constructing path matrix,the line structure normalization was implemented and a general method for path length calculation was proposed.A lot of simulation results show that the location algorithm is accurate and effective.
What problem does this paper attempt to address?