Numerical Simulation of Thermal Performance of Indirect Dry Cooling Tower Under Different Operation Modes of Sectors

MA Huan,SI Fengqi,LI Lan,YAN Wensheng,ZHU Kangping
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2015.18.014
2015-01-01
Abstract:ABSTRACT:A 600MW dry cooling tower was taken as an example, and flow distribution model of circulating water and numerical model of the tower were established respectively. In order to research the effects of crosswind on thermal performance of the tower, numerical simulations were carried out in different conditions of all sectors operating, side sectors shut down and upwind sectors shut down. The results show that when side or upwind sectors are shut down, other sectors have higher heat rejection and lower temperature drop of circulating water compared with the way of all sectors operating at low wind speed. Whereas these sectors have different variation of thermal performance influenced by complex flow fields inside or outside the tower and the interactions between sectors at high wind speed. Meanwhile combining cooling efficiency and freezing prevention of the tower, instructional views are provided for the economical and safely operation of the unit.