Testing and numerical simulation of natural draft cooling tower

Tianle HU,Xiaoyun XIE,Yi JIANG
DOI: https://doi.org/10.3969/j.issn.1002-3364.2016.07.115
2016-01-01
Abstract:Through practical measurement on a natural draft cooling tower in a 150 MW unit,the efficiency and coefficient of heat and mass transfer in the tower were obtained,and several problems during the tower operation and its performance optimization direction were found.On this basis,the temperature and pres-sure distribution in rain area and filling area of the cooling tower were numerically simulated.The results show that,with the filling material thickness of 3.0 m inside the cooling tower,42.1% temperature drop needs 55.8% pressure loss,and the optimum thickness of the padding is around 2.5 m.The optimum oper-ation strategy of this circulating cooling water pump is one pump with two towers,and the wet bulb effi-ciency of the cooling tower can reach 75.0%,the net power generation can increase by 3.007 MW com-pared with the unit using two pumps with one tower strategy.