Numerical study on the effects of layout compactness of the annular-aligned moist media on thermo-hydraulic performance of an indirect dry cooling tower

Huan Ma,Liang Cai,Fengqi Si
DOI: https://doi.org/10.1016/j.applthermaleng.2022.118649
IF: 6.4
2022-08-01
Applied Thermal Engineering
Abstract:It is necessary to address the low-efficiency operation of an indirect dry cooling tower (IDCT) under adverse ambient conditions. Annular-aligned moist media outside the tower base is an integrated solution by performing inflow air precooling and flow field reconstruction to improve thermo-hydraulic performance of the tower. In this work, a three-dimensional (3D) numerical model was developed to evaluate the synergy between the air precooling effect and windbreak-like effect of moist media with varied interval angles. The results indicate that under moist media scheme of any interval angle, the air precooling effect enhances steadily with wind speed, but the windbreak-like effect or the combined effect of the moist media turns to decline as wind speed exceeds 8 m/s. The air precooling effect is stronger than windbreak-like effect in improving tower performance at low and ultra-high wind speeds. Under the identical windy condition, the windbreak-like effect of the moist media enhances with the interval angle, while the air precooling effect varies little. The media with an interval angle of 10° working in dry (wet) mode maximize cooling capacity of the IDCT by 17.7% (26.9%). Water consumption for unit cooling capacity increment of the IDCT generally ranges from 0.6 kg/MJ to 0.8 kg/MJ.
energy & fuels,engineering, mechanical,thermodynamics,mechanics