Optimization on Inlet Deflectors Structural Parameters of a Natural Draft Counter-flow Wet Cooling Tower

HU Danmei,ZONG Tao,ZHANG Zhichao,ZHANG Jianping
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2013.11.014
2013-01-01
Abstract:Cooling tower is important cooling equipment,its performance that has a direct effect on security,stability and economy of a power plant can be greatly affected by the environmental cross-wind.The method of installing the deflectors in air inlet of cooling tower was taken.In the case of a natural draft wet cooling tower(NDWCT) of a 300MW power plant,based on CFD code FLUENT,the flow and heat transfer characteristics in the cooling tower with deflectors were numerical simulated.The simulation results show that: the deflectors can increase the air velocity and disturbance in center region and strengthen the heat transfer in the cooling tower,so that cooling performance can be improved.The relatively best installation angle of deflectors is 45°.The optimal length and installation number of deflectors are 6m and 40 pieces respectively.Under the same situation,compared with rectangle deflector,the outlet temperature from cooling tower with type A deflector can be lowered by 0.0546℃,the cooling effect from type B and C deflectors are worse than the rectangle deflector.