Analysis on asymmetric fault current characteristics of inverter interfaced distributed generator under positive-sequence and negative-sequence current respective control strategy

Zhongxue CHANG,Zhongli YANG,Guobing SONG,Wei HUANG,Yongheng KU,Gaofeng SU,Xinming WANG
DOI: https://doi.org/10.16081/j.issn.1006-6047.2018.01.006
2018-01-01
Abstract:In order to reveal the fault characteristics and fault mechanism of IIDG(Inverter Interfaced Distributed Generator),the fault current expressions under independent control strategy of positive-sequence and negative-sequence components are deduced based on the thought of power balance and controllable characteristics.Then the influencing factors of fault current are analyzed.The analytical results show:the d-axis and q-axis components of positive-sequence and negative-sequence currents are second order response to voltage dip,and the trend of the three-phase positive-sequence and negative-sequence currents are firstly increasing gradually and then decreasing to a steady value due to the overshoot of second order response;the steady-state value of the positive-sequence and negative-sequence currents are related to the active power output,reactive power output and positive-sequence and negative-sequence voltages,and transient characteristics are closely related to control parameters of converter and current phase at the moment that fault occurs.Simulation on PSCAD and recording data verify the correctness of the theoretical deduction.The proposed analysis method can effectively reflects the fault characteristics of IIDG and provide theoretical reference to fault characteristic analysis of inverter's interfaced components and related relay protection.