Simulation and Experimental Research on Lightning-caused Breaking Mechanism of 10 kV Overhead Line

Yuan GAO,Xuedong SUN,Zhe ZHANG,Guowei GE,Minfu LIAO,Yongsheng ZHANG,Honggao LI
DOI: https://doi.org/10.13296/j.1001-1609.hva.2017.08.022
2017-01-01
Abstract:In order to ascertain lightning-caused breaking mechanism of 10 kV overhead transmission lines and improve the liability of distribution network system,in this paper,from 2 aspects of the simulation and experimental research,the lightning-caused breaking mechanism are analyzed.A mathematical model of multiple physical field coupling during lightning-caused breaking is established.The influence of interaction of heat,electricity,magnetism and force on the course of lightning-caused breaking is analyzed.The 10 kV line lightning test platform is built,the lightning breakdown point distribution test is carried out,and the arc plasma discharge diagnosis and arc shape evolution process,micro mechanism of internal lightning are analyzed.The simulation and test results show that lightning flashover position is in the insulator near 100~200 mm.According to the power supply position,two kinds of simulation models are established.When the power supply position on the left side,arc root is steady combustion at a position after 0.03 s,then lightning-caused breaking fault may occur.Therefore,the paper provides the basis for the lightning-caused breaking protection of 10 kV overhead transmission lines.
What problem does this paper attempt to address?