Positioning Method for Fault Section Based on Wide Area Measurement

LI Zilong,JIANG Xiuchen,LIU Hao,WANG Yifeng
DOI: https://doi.org/10.3969/j.issn.1007-290X.2017.08.012
2017-01-01
Abstract:Due to the wide adoption of non-effective grounding mode for neutral point of power distribution network and weak characteristic quantities of faults such as single-phase grounding, there are short of effective and reliable methods for fault line selection and fault positioning.Therefore, this paper analyzes characteristic of zero sequence current in the overall process of fault, defines standard deviation degree of zero sequence current of adjacent detection points and presents a positioning method for fault section based on wide area measurement system(WAMS).By combining accuracy and rapidity of collecting data under the WAMS, it uses standard deviation degree of zero sequence current wave in the overall process of fault happening and action of the compensation device to locate the fault section.Finally, simulation on PSCAD/EMTDC verifies the feasibility and reliability of the proposed method.
What problem does this paper attempt to address?