Thermal analysis for multi-conductor bundle in high voltage overhead transmission lines under the effect of strong wind
Wentao Yang,Zhi Zheng,Wei Huang,Danhua Chen,Jie Yuan,Yishi Yue,Zezhong Sun,Qiuqin Sun
DOI: https://doi.org/10.1016/j.epsr.2024.110308
IF: 3.818
2024-03-16
Electric Power Systems Research
Abstract:Bundle conductors are widely used in HV transmission lines to suppress the corona discharge and reduce the line reactance. To determine its current ampacity of multi-conductor bundle, the thermal analysis is indispensable. A three-dimensional flow-thermal coupling model of multi-conductor bundle considering the effect of strong wind is developed in our study. Using the finite element method, both the temperature field and the fluid field are computed; the characteristics for the multi-physics fields are discussed; the interaction between the fields as well as the mutual influence between subconductors are elucidated. Moreover, a set of sensitivity analysis have been performed, and the effects of load current, conductor spacing, wind speed on temperature field and fluid field are investigated. Based on the pitch-diameter ratio, a novel method to improve the thermal performance of multi-conductor bundle is proposed. Finally, the optimized structure is obtained, and the current ampacity is expected to be greatly enhanced.
engineering, electrical & electronic