Windage yaw dynamic analysis methods for transmission lines considering aerodynamic damping effect

Wen-juan LOU,Yue YANG,Zhong-bin L,Shao-feng ZHANG,Lun YANG
DOI: https://doi.org/10.13465/j.cnki.jvs.2015.06.005
2015-01-01
Abstract:Electrical power transmission systems are severely threatened by flashover accidents caused by windage yaw.Here,a nonlinear dynamic transmission line model consisting of three-span electrical conductors was established precisely by using the finite element method.Then,the fluctuating wind speed field around the transmission line was built with the harmonic wave superposition method and the time-varying wind loads acting on the line were simulated with the quasi-steady assumption.The time and space correlation characteristics between different simulated points were taken into account.Furthermore,the impact of aerodynamic damping caused by conductor movements on the windage yaw dynamic response of the transmission line was investigated.The aerodynamic damping gained with the US transmission line design code ASCE No.74 was adopted to compute the windage yaw dynamic response of the line.The results of the two methods were compared.It was shown that the aerodynamic damping can reduce the maximum value of the windage yaw dynamic response of the line significantly,but have no remarkable effect on its average value;the results of the two methods are close to each other.