Response Characteristics and Frequency-domain Calculation Method of Dynamic Wind-induced Deflection of Transmission Lines

Wenjuan LOU,Gang LUO,Xiaohui YANG,Ming LU
DOI: https://doi.org/10.13336/j.1003-6520.hve.20170428014
2017-01-01
Abstract:The equilibrium configuration and stiffness of a multi-span conductor under gravity and mean wind load are taken as the initial conditions for calculation.The fluctuating wind-induced response of the conductor is assumed to be small deformation.Method recommended by the American Society of Civil Engineers (ASCE) is applied to take the effects of aerodynamic damping into account.Frequency-domain calculation method of dynamic wind-induced deflection is proposed.The influences of vibration modes and combination methods on calculation results are deeply analyzed and the results are compared with those obtained by time-domain method.The comparison shows that multiple vibration modes must be considered in the dynamic wind-induced deflection analysis and the cross-terms cannot be neglected.For a 2-span conductor,the complete quadratic combination (CQC) of the first three modes can meet the precision requirement.For a 5-span conductor,the CQC combination of the first nine modes can meet the precision requirement.The calculation shows that the peak fluctuating response of a suspension insulator string can reach more than 10 percent of the mean response,therefore the ignorance of fluctuating wind-induced deflection in current transmission line design is not safe and is one of the main causes of flashovers.