Wind-induced response and wind load factor of transmission tower under terrain B wind field and typhoon wind field

Wenjuan Lou,XIA Liang,JIANG Ying,JIN Xiao-hua,WANG Zhen-hua
DOI: https://doi.org/10.3969/j.issn.1000-3835.2013.06.003
2013-01-01
Abstract:A numerical analysis on the wind-induced response of a four-circuit angle-steel transmission tower under conventional terrain B wind field and typhoon wind field was performed.A FEM model was established,and the dynamic response was calculated under a fluctuating wind field simulated by using harmonic wave superimposing method.Based on data of numerical analysis,wind-induced responses under each wind field were discussed.Essential conclusions are as follows:high turbulence and strong variability of typhoon wind field have great influence on the response of transmission towers.The RMS of acceleration under typhoon wind field is larger than that under terrain B wind field.Under the two types of wind fields,the average ratio of wind load factor is about 1.25.Therefore,the design of transmission towers in typhoon-prone areas should take the fluctuating wind load magnification effect into consideration.Furthermore,the wind tunnel test on an aeroelastic model of the transmission tower was performed to study its wind-induced responses under different velocity.The test results were compared with theoretical values and the accuracy of the numerical analysis was verified.