Influence of Buildings on Electric Field Generated by HVAC Transmission Lines

Xiu-li LIN,Xin-hua XU,Da-hui WANG
DOI: https://doi.org/10.3969/j.issn.1003-6520.2007.04.018
2007-01-01
Abstract:The simulated charge method (SCM) is adopted to calculate the distribution of the power frequency electric field generated by the double-circuit HVAC transmission lines with different conductor configurations in the paper. The results indicate that the conductor radius and the distance of the phase-phase affect the maximum power frequency electric field intensity, and little affect the distribution and attenuation of the power frequency electric field intensity when the distance is far from 5m. The height of the conductor has main effect on the attenuation and distribution of the power frequency electric field intensity. In order to illustrate the effect of the buildings on the distribution of power frequency electric field, on-site measurements were carried out along two lines. The measured lines are perpendicular to the way of the double-circuit transmission lines, one of which is located in a smooth place and the other is located between two buildings. Comparisons between the calculated and measured power frequency electric field intensity indicate that the buildings have the shielding effect on the power frequency electric field.