Electromagnetic Field in Home Near High Voltage Transmission Line and Shielding Efficiency of Structure

Zhen MEI,Shui-ming CHEN,Feng MA,Cheng-gang DENG
DOI: https://doi.org/10.13336/j.1003-6520.hve.2008.01.026
2008-01-01
Abstract:The domestic electric and magnetic fields (EMF) of three different locations, between 5 Hz~100 kHz, caused by the nearby high voltage transmission line, are examined with a PMM 8053A General Purpose Field Meter, which has the ability of timing measurement and data output, together with Probe EHP-50A. Firstly, the results of previous relevant studies, the methods of measurement as well as the reference levels for safe general public exposure are presented. Accordingly, the measurement design is determined. Secondly, the results of the electric and magnetic-field for above-mentioned locations, where the measurements have been carried out, are evaluated. The measured data are much less than the limit value 4 kV/m and 100 μT according to the technical evaluating regulation of electromagnetic environment of 500 kV EHV transmission and substation project. Finally, based on the evaluation of these results, according to the safe guidelines, some conclusions are drawn as follows: The influence of the high-voltage transmission line on the domestic electric and magnetic fields reduces with the increase of the distance between them; The shielding efficiency of structures for power frequency electric field is outstanding, while appliances are the most important resources of the magnetic field. Besides, different types of structures have distinctions in shielding efficiency-the structures of reinforced concrete has superior shielding efficiency (19.5%~39.1%) to general mud and brick structures(8.79%~11.27%), and they both shield the electric field perfectly.
What problem does this paper attempt to address?