Electrostatic Discharge Effect on Safe Distance Determination for 500 Kv Ac Power Line'S Helicopter Inspection

Shuwei Wan,Xingming Bian,Lan Chen,Deming Yu,Liming Wang,Zhicheng Guan
DOI: https://doi.org/10.1016/j.elstat.2013.06.001
IF: 1.942
2013-01-01
Journal of Electrostatics
Abstract:The effect of electrostatic discharge on safe distance determination for 500 kV ac transmission line's helicopter inspection is investigated. Potential difference exists while helicopter is near the power transmission line, which is harmful to the inspection persons. The electric field in the helicopter cabin is calculated when it is near the power line. The result indicates that the potential difference becomes higher with the decrease of the distance between the helicopter and transmission line. Considering the discharge energy and the guarantee of the persons' safety, the safe distance for 500 kV ac transmission lines is determined as d >= 15 m. (C) 2013 Elsevier B.V. All rights reserved.
What problem does this paper attempt to address?