Simulation of Effect on 500 Kv AC Transmission Line Electric Field of Patrol Helicopters

WANG Liming,YU Deming,CHEN Fangdong,WAN Shuwei,BIAN Xingming,CHEN Lan
DOI: https://doi.org/10.3969/j.issn.1003-6520.2013.01.029
2013-01-01
Abstract:The determination of electromagnetic safety distance in helicopter power line patrol is the assurance for operators.Thus,the field distribution was calculated using a finite element software.In the beginning of the calculation,the transmission line model was simplified and verified by the image method.Then the field distortion near the helicopter was acquired at different positions and different distances when the helicopter was floating near the 500 kV transmission lines.The calculation result shows that,when no helicopter exists,the electric field strength around a transmission line is inversely proportional to the distance from the lines;when a helicopter exists,its maximum electric field strength is inversely proportional to its distance from the transmission.The maximum strength on the helicopter normally appears at the helicopter wing and is 6-10 times that without helicopter.Moreover,if the helicopter is near the earth wire,because of the shielding effect of grounding line,the helicopter's field strength becomes lower so as not to affect the helicopter inspection.According to the relationship of the maximum strength and the distance from helicopter to lines,the safety distance at different electric field intensity limit-values could be determined,e.g.,it is about 2.2 m with a limit-value of 500 kV/m.
What problem does this paper attempt to address?