Comparison of Performance between O_3-BAC and GAC Processes

Wang Zhan-sheng
2006-01-01
Abstract:To remove organics effectively and to confirm whether it is necessary to add O_3 before granular activated carbon (GAC) filtration, an experiment was carried out. The removal effects of O_3-BAC and GAC on COD_ Mn, UV_ 254, TOC and their abilities of biostable improvement were compared. The result indicates that the average removal rates of O_3-BAC for COD_ Mn, UV_ 254, TOC are 10.3%, 11.1%, 7.1% higher than GAC, respectively. The AOC removal rate of O_3-BAC is above 80% and the effluent AOC is 25.9-46.4 μg acetate-C/L. The effluent is biostable. The AOC removal rate of GAC is about 40% and the effluent AOC is 85.8-117.6 μg acetate-C/L. Sometimes the effluent isn’t biostable. As a conclusion, ozonation can improve the removal rate of organic pollutants, extend the service time of AC and enhance the biodegradation ability of AC filter.