Impulse Oscillator Circuit of Turn-to-turn Over-voltage Test for Air-core Reactors

XU Lin-feng,LIN Yi-feng,WANG Yong-hong,WEI Xin-lao,CHEN Qing-guo
DOI: https://doi.org/10.3969/j.issn.1007-2683.2011.06.008
2011-01-01
Abstract:Many standards have already permitted to do the impulse oscillator turn-to-turn over-voltage test for dry-type air-core reactors.In order to search the operational feasibility of the test,analyses and experiments on the impulse oscillator circuit are carried out in this paper.Because quickly and repeatedly charging a capacitor and directly discharging it though sphere gaps into the reactor is required,the impulse oscillator circuit is different from a traditional impulse voltage generator.Charging the capacitor can be performed by a half-wave rectifying circuit;the stabilized test voltage which is meeting the standard code value can not be applied on the reactor by the circuit with natural spark-discharge of sphere gaps because of the influence of aeroinization.It is found by experiments that the working state of sphere gaps is controllable by a trigger in the repeatedly discharge condition and the stabilized impulse oscillator voltage can be applied on the reactor due to the longer sphere gaps of controllable spark-discharge than that of natural spark-discharge in the same applied voltage.Research results indicate that the controllable spark-discharge technique is necessary and feasible to ensure the implementation of the turn-to-turn over-voltage test for dry-type air-core reactors.
What problem does this paper attempt to address?