PIV and thermal-vision experimental and numerical investigation on the airside performance of slotted fin surfaces
hongzhi li,haijun wang,mingyu yao,lixin zhang,hongfang gu,jianping nie
DOI: https://doi.org/10.1016/j.ijheatmasstransfer.2014.11.039
IF: 5.2
2015-01-01
International Journal of Heat and Mass Transfer
Abstract:Experimental and numerical analyses were carried out to study the fluid flow and heat transfer characteristics of two slotted fin surfaces (X-type and Arc-type) in fin-and-tube heat exchangers. Experiments were conducted by using PIV and infrared thermal-vision systems. Good agreement was found between numerical and experimental data under the Reynolds number ranging from 558 to 2235. The results showed that the heat transfer performance of the X-type fin surface was superior to that of the Arc-type fin surface due to more reasonable strips arranging along the flow direction for periodical renewal of the flow and thermal boundary layers, although the Arc-type fin surface could improve the flow pattern and heat transfer characteristics in the weak recirculation zone behind the tube. However, the pressure drop of the X-type fin surface was higher than that of the Arc-type fin surface. A novel improved slotted fin surface (Butterfly-type) was proposed and proved to exhibit the best overall performance. The results of the performance evaluation for the three slotted fin surfaces revealed that the Butterfly-type slotted fin surface could: 1. increase heat duty by approximately 20–24% for FG (fixed geometry) and IPP (identical pumping power). 2. Reduce pumping power by approximately 38–51% for FG and IHD (identical heat duty). 3. Reduce heat exchange surface area by approximately 21–25% for IPP and IHD. Finally, analysis from the view point of the field synergy principle demonstrated that the improved Butterfly-type slotted fin surface could appreciably reduce the domain average synergy angle between the velocity and temperature gradient, and hence, improve the synergy between the two fields.