Flow Distribution Properties of Header Configuration in Plate-Fin Heat Exchangers

Tian Jinjin,Zhang Zhe,Li Yanzhong,Li Man
DOI: https://doi.org/10.3969/j.issn.1005-9954.2009.01.005
2009-01-01
Abstract:The influences of the conventional header configuration on the fluid flow distribution in plate-fin heat exchanger were numerically investigated.The numerical calculation results show that the fluid flow maldistribution is very serious in the heat exchanger.The maximal degree of flow nonuniformity can reach 0.56 when the average Reynolds is 1 000.On the basis of the analysis of the fluid flow maldistribution,the header configuration with curving perforated baffle was brought forward for the first time.The computational results indicate that the improved header configuration can effectively improve the performance of fluid flow distribution in the heat exchanger.The fluid flow distribution for the header configuration with curving perforated baffle is more uniform than that for the header configuration with plane perforated baffle.The absolute degree of fluid flow nonuniformity in plate-fin heat exchanger is reduced from 3.47 to 0.32 by changing the header configuration.The numerical results agree well with the experimental results.It indicates that the mathematical model and the calculating method are reliable.
What problem does this paper attempt to address?