Effect of different improved header on flow and pressuredifference in plate-fin exchangers

Zhou Aimin,Li Yanzhong,Wen Jian
DOI: https://doi.org/10.3969/j.issn.1001-4578.2006.05.003
2006-01-01
Abstract:The effect of 3 different header configurations with different Re on the characteristics of internal flow distribution and drag distribution of a plate-fin heat exchanger is investigated. The experiment result indicates that the maldistribution would be caused by the ordinary industrial header for the internal flow of the plate-fin heat exchanger, while the maldistribution parameters and the maximum velocity ratio can be effectively reduced by perforated plate header configuration, the effect of flow distribution can be greatly improved, the effect will be more obvious with the increase of Re. it is also found out that more maldistribution of flow drag would be caused by maldistribution of flow. It is considered that Re is the critical factor influencing the both, while the improvement of staggered perforated plate header configuration is of optimal effect.
What problem does this paper attempt to address?