Influential Factors of Pulse Injection from Outer Semi-conductive Layer of Cable with PEA Measurement Technology

Xia WANG,Chi CHEN,Jinzhou XIONG,Kai WU,Mingli FU,Shuai HOU
DOI: https://doi.org/10.13336/j.1003-6520.hve.20171031011
2017-01-01
Abstract:In the coaxial cable space charge measurement system based on pulsed electro-acoustic (PEA) method,the space charge measurement signal has a direct relationship with the coupled pulse.Firstly,we improved the pulsed electro-acoustic(PEA) space charge measurement technology.Then,we measured the space charge wave of 10 kV coaxial cable with different distances from ground point to pulse injection point.Finally,we experimentally researched the influential factors including different ground points,different cable size,and different length of pulse injection area to pulse injection waveform through simulation.The results show that the injected pulse waveform directly influences the space charge signal.When pulse is injected from cable outer semi-conductive layer,the impedance characteristic of semi-conductive layer can influence the pulse injection.And the grounding point and the size of coaxial cable will affect the injection of pulse.The farther the distance from ground point to pulse injection point is,the higher the pulse amplitude will be.Besides,the diameter of outer insulation can influence the equivalent resistance of outer semi-conductive layer.
What problem does this paper attempt to address?