Study on Characteristic Parameter Selection of Alternating Current Filter Sub-Bank Circuit Breaker

Chen Weimin,Chu Jinwei,Zhang Changhong,Yang Xu,Li Weiguo,Zhou Haibin
DOI: https://doi.org/10.1109/icempe.2017.7982083
2017-01-01
Abstract:As alternating current filter (ACF) sub-bank circuit breakers in DC transmission projects have been switched frequency and withstood AC/DC hybrid over-voltage, it is necessary to research the selection of characteristic parameter of ACF sub-bank circuit breakers in order to guarantee the safe operation. Operation and maintenance data in China Southern Power Grid Company Limited of the latest 15 years has been sorted and analyzed, which displayed that ACF sub-bank circuit breakers in converter stations have been more likely to appear insulation breakdown defect than ordinary circuit breakers in transformer substations. Combined with the calculation of the over-voltage in such an abominable operating condition, it is suggested that ACF sub-bank circuit breakers should be suitable for higher operational requirements instead of choosing the same insulation level with the ordinary circuit breakers, while some measures could be taken to improve capacitive current switching capability and transient recovery voltage(TRV) in the arc chamber.