Drawn Vacuum Arc Behaviors of 1/2 Coil-Type Axial Magnetic Field Contact

Xiaoshe Zhai,Sandeep Kulkarni,Xiaofei Yao,Viren Kumar Acharya,M. Hemachander,Wei Zhang
DOI: https://doi.org/10.1109/deiv.2016.7748718
2016-01-01
Abstract:The objective of this paper is to investigate the transition of drawn vacuum arc anode discharge modes of the 1/2 coil-type axial magnetic field contacts. The diameter of the contact used in the experiment include 60 mm and 63 mm. The opening velocity is 1.5 m/s from the contact separation to the 75% of full contact stroke of 15 mm. A dynamic solid angle ΩI as well as ΩII is used to evaluate the transition of anode discharge mode. Either the ΩI or the ΩI is defined as a ratio of contact diameter on contact separation, at which the transition from intense arc mode to diffuse arc mode or from the diffuse arc mode to the anode spot mode occurs, respectively. Test results show that the transition from intense arc mode into diffuse arc mode is dominated by the ΩI, rather than the axial magnetic flux density Baxial. However, the transition from diffuse arc mode into anode spot mode is dominated by the Baxial, rather than the ΩII. The arcing interval tI, from the initiation of vacuum arc to the evolving of the intense arc mode into diffuse arc mode, increases with the decreasing of ΩI, and with the increasing of Baxial. The arcing interval tII, from the initiation of vacuum arc to the formation of the anode spot, increases with the decreasing of ΩII, and with the increasing of Baxial.
What problem does this paper attempt to address?