Experimental Investigation of Vacuum Arc Characteristics Subject to Axial Magnetic Field Contacts with Different Ratios of Diameter to Gap Distance

Hongda Wang,Lijun Wang,Qiang Ma,Zhiwei Wang,Zhefeng Zhang,Wenzhe Zhang
DOI: https://doi.org/10.1063/5.0108725
IF: 2.2
2022-01-01
Physics of Plasmas
Abstract:In this study, to investigate vacuum arc characteristics under different diameter-to-gap distance ratios (D/g), experiments are conducted on axial magnetic field (AMF) contacts with varying D/g. The peak current value ranges from 15 to 35 kA. The experimental results show that the ability of AMF contacts to control the arc decreases with D/g. Furthermore, the 2/3 coil contact can control the arc under long gap distances, whereas the cup-shaped contact cannot effectively control the arc under long gap distances. The arc energy and noisy period duration decrease with increasing D/g. The arc voltage of the 2/3 coil contact at the peak moment is always the lowest compared to the cup-shaped contact and the 1/2 coil contact, and the arc voltage of the 2/3 coil contact at the peak moment has an approximate power function relation with D/g. The simulation results show that the AMF distribution changes from saddle shape to bell shape with decreasing D/g. The 2/3 coil contact is more suitable for high-voltage vacuum interrupters (VIs), while the cup-shaped contact is more suitable for medium-voltage VIs.
What problem does this paper attempt to address?