Comparison of Vacuum Arc Behaviors Between Axial-Magnetic-Field Contacts

Zhiyuan Liu,Shaoyong Cheng,Yuesheng Zheng,Mingzhe Rong,Jimei Wang
DOI: https://doi.org/10.1109/tps.2007.914184
IF: 1.368
2008-01-01
IEEE Transactions on Plasma Science
Abstract:We compared vacuum arc behaviors of three slot-type axial-magnetic-field (AMF) contacts at two fixed contact gaps using high-speed digital photography and arc-voltage measurements. Solid angle is subtended by anode at the center of cathode or the ratio of the anode diameter to the gap length (D/g). With coupled influence of the AMF, we observed that with the D/g ratio 48 mm/14 mm, the arc kept in low current modes until higher current compared with the D/g ratio 48 mm/8 rum case. With the D/g ratio 58 mm/14 mm, the arc-mode transitions with the increase of current were similar as the D/g ratio 58 mm/8 turn case. However, with the D/g ratio 66 mm/14 mm, the arc became high current modes at lower current compared with the D/g ratio 66 mm/8 mm case. Correspondingly, with the D/g ratio 48 mm/14 rum, arc voltages at current peaks were close to the D/g ratio 48 mm/8 rum case, whereas arc voltages at current peaks with the D/g ratio 58 mm/14 nun were close to that of the 58 mm/8 mm case. However, with a contact diameter of 66 mm, the arc voltages with the D/g ratio 66 mm/14 mm were higher than the 66 mm/8 rum case. The arcs with the D/g ratio 66 mm/8 rum were more diffuse than the 48 mm/8 rum case. Moreover, the arcs with the D/g ratio 66 mm/14 mm were also more diffuse than the 48 mm/14 mm case when the current peak was 17.8 kA and above. The relationship between interrupting capacity of vacuum interrupters with the slot-type AMF contacts could be expressed as I = k x (D/g) + b, where k and b are constants.
What problem does this paper attempt to address?