Calculation of Transient Overvoltage in AC Submarine Cable System

XUAN Yaowei,ZHENG Xinlong,CHENG Binjie,XU Zheng
DOI: https://doi.org/10.13296/j.1001-1609.hva.2014.09.001
2014-01-01
Abstract:To analyze the transient overvoltage caused by single-phase short circuit or three-phase short circuit in AC submarine cable system, simulation models were built on the platform PSCAD/EMTDC. For the neutral point grounded AC submarine cable system rated at 110 kV and the neutral point isolated AC submarine cable system rated at 35 kV, the overvoltage was calculated in the conditions of different transmission power, transmission distance, and short circuit capacity, and the relationship between the maximum overvoltage and these variables was analyzed. Moreover, the physical mechanism was discussed. This study may provide a reference for determining system parameters and insulation levels of submarine cable lines and substations.