Simulation of AC and DC Electric Field for 800 kV Grade High Voltage Disconnector
Ji-huan TIAN,Yan-chao SHA,Yuan-xiang ZHOU,Yu-zhou SUN,Ke-ke SUN,Zhan-jie WANG
2011-01-01
Abstract:The electric field calculation is important to the structure optimization of the disconnecting switch, the control of the corona loss, the audible noise, and the radio interference level. Consequently, the ANSYS software was used to calculate the AC and DC electric field distribution and to determine the value and the position of the maximum electric field. On the basis of static electric field theory, in the DC field calculation, the steady conduction current field theory was used to calculate the potential distribution on the surface of the disconnector. When the resistivity ratio between different materials was beyond 10 orders of magnitude, the problem of divergent values solved by ordinary finite element method would occur. Therefore, it was proposed that, according to the structure feature of the disconnector, the floating potential of the metal connectors was obtained by calculating the resistances of the supporting insulators firstly. Then the surface potential of the insulators was derived, which was in linear relation with the surface distance. Secondly, with the surface potential distribution of the disconnector, the ANSYS sub-modeling technique was adopted to calculate the electrostatic field distribution in the air domain. Hence, the coupling between conduction current field and static electric field was achieved. Finally, the AC and the DC field results were summarized and compared. The DC field simulation results show that the potential distribution at the interface between disconnector and air domain is continuous, which verifies proposed method.