Analysis of Radiated Interference of 10kv Intelligen T Distribution Switch

Kejian Chen,Zhicheng Ma,Hai Jin,Xiaoying Zhang,Qiang Zhou,Zhengqiang Liu
DOI: https://doi.org/10.1109/ichve49031.2020.9279721
2020-01-01
Abstract:With the rapid development of smart grid and grid automation level, the intelligent requirements of power switch in the power system are also increasing. One of the main factors that lead to the secondary equipment failed is the transient electromagnetic interference in the process of switching operation. Due to the transient electromagnetic interference(EMI) caused by the operation of intelligent distribution switch, the secondary equipment may not work normally. Especially during the operation of intelligent distribution switch, the burning and reignition of the arc which caused by contacts generate transient electromagnetic field on the disconnected bus and radiate energy to the surrounding space. Therefore, it is of great theoretical and practical significance to research the electromagnetic interference of 10kV distribution switch in secondary control and protection device. In this paper, the finite-integral time-domain (FITD) method is used to calculate the interference of 10kV intelligent distribution switch when it is operating. The calculated results show that the space radiation and coupling interference caused by the arc in the 10kV distribution switch can be ignored because the intelligent distribution switch is a closed container.
What problem does this paper attempt to address?