Pressure Characteristics of Dissolved Acetylene in Transformer Oil Based on Photoacoustic Spectroscopy Detection

Chen Weigen,Wan Fu,Zhou Qu,Zhao Lizhi,Liao Chao
DOI: https://doi.org/10.3969/j.issn.1000-6753.2015.01.015
2015-01-01
Abstract:Dissolved gas analysis(DGA) method is one of the most effective means in fault diagnosis of power transformer. Gas photoacoustic spectroscopy(PAS) can be well applied in gas detection. The effect of gas pressure on the photoacoustic spectroscopy detection is significant. Functional relations between gas pressure and gas absorption coefficient, resonant frequency, quality factor, photoacoustic cell constant and PA voltage(PAV) signal are derived theoretically in this paper. Based on the constructed tunable experimental setup, experimental detection of the acetylene dissolved in transformer oil was done. The experimental results show the correctness of the functional relations above and that PAV signal has a good linear dependence on the 1.5th root of pressure P(0<P<75kPa) and the square root of P(75kPa<P<100kPa) when without gas absorption saturation effect. Taking consideration of absorption line broadening and the change rule of PAV signal, the best gas pressure for the photoacoustic spectroscopy detection of acetylene absorption line 6 578.58cm-1 is 75kPa. The theoretical and experimental results provide technical support for further improvement in photoacoustic spectroscopy on-line monitoring for oil gas.
What problem does this paper attempt to address?