A highly sensitive low-pressure TDLAS sensor for detecting dissolved CO and CO 2 in transformer insulating oil

Zhao Li,Qirui Zhang,Zhentao Wang,Jingmin Dai
DOI: https://doi.org/10.1016/j.optlastec.2024.110622
IF: 4.939
2024-01-20
Optics & Laser Technology
Abstract:Dissolved Gas Analysis (DGA) is widely used for monitoring and diagnosing the health status of power transformers. A highly sensitive low-pressure tunable diode laser absorption spectroscopy (TDLAS) sensor was developed and evaluated for the detection of dissolved carbon monoxide (CO) and carbon dioxide (CO 2 ) in transformer insulating oil. The sensor addressed the issue of headspace gas dilution caused by the volume of multipass gas cells, thus improving the minimum detection limit (MDL) for dissolved gases. Firstly, an analysis was conducted to determine the essential parameters required for the sensor. These parameters included an operating pressure of 0.1 atm and optimal modulation depths of 4.1 and 4.4. Subsequently, the sensor was calibrated using a mechanical oscillation gas chromatography (MO-GC) method. At 0.1 atm, the gas extraction ratios for the low-pressure dynamic headspace sampling unit were 8.25 and 4.5 for CO and CO 2 , respectively. The Allan variance analysis revealed that the equivalent MDL for dissolved CO was 0.147 ppm, while for dissolved CO 2 , it was 0.9 ppm. Finally, comparative experiments with different oil samples showed measurement errors of less than 6 ppm or 6 %. Continuous measurements resulted in relative standard deviations (RSDs) of less than 4 %, validating the precision and repeatability of the sensor.