Application of Photo-acoustic Spectroscopy Technology to Dissolved Gas Analysis of Oil-immersed Power Transformer

Yuan Wang
2013-01-01
Abstract:As the power system expands and develops fast,the on-line fault inspection for transformer is getting more and more attentions.This paper discusses the principle and system of transformer dissolved gas on-line monitoring which is based on the Photo-Acoustic spectroscopy.The reliability of Photo-Acoustic technology has been proved through comparing and analyzing the Photo-Acoustic spectroscopy and Gas Chromatography.The MULTITRANS system which is based on Photo-Acoustic spectroscopy is presented as well.
What problem does this paper attempt to address?