Quantitative Analysis of FTIR Used in Transformer On-line Monitoring

LI Hong-lei,ZHOU Fang-jie,TAN Ke-xiong,GAO Wen-sheng
DOI: https://doi.org/10.3321/j.issn:1000-1026.2005.18.012
2005-01-01
Abstract:Currently, the chromatographic column and gas sensor are widely used in online monitoring devices of dissolved gases in transformer oil. But there exist disadvantages with these devices, such as, the consumption of carrier gas, the requirement of regular calibration, etc. Since FTIR (Fourier transform infrared) is highly accurate, consumes no carrier gas and requires no calibration, the application of FTIR in such monitoring devices is studied. Experiments on the flow gas method have been designed. And the FTIR spectrometer is used to collect the infrared spectra of C2 H2 , which is the most important gas for transformer fault diagnosis. Curve fitting of the output of FTIR is performed, and the effects of quantitative characteristics and concentration range on the quantitative analysis are discussed. In addition, the lowest detection limit to FTIR is tested. Experiment and calculation results show, that by taking the peak height in the low concentration range or peak area in the high concentration range as the quantitative characteristic, using the cubic polynomial to fit the output curve of FTIR, the accuracy can be improved. The lowest detecting limit with 2.4m gas cell is below 0. 3 μL/L and that of 10 cm gas cell is below 3μL/L.