Experimental Investigation of Transient Earth Voltage and Acoustic Emission Measurements of Partial Discharge Signals in Medium-Voltage Switchgears
Liuhuo Wang,Haijing Wang,Lijun Wang,Hong Lu,Wenjun Ning,Shenli Jia,Ji Wu
DOI: https://doi.org/10.1109/icepe-st.2013.6804296
2013-01-01
Abstract:Partial discharges (PDs) are small electrical sparks that can occur in insulation systems in high-voltage equipment, and if it is kept for a long time, electric equipment and power grid will become very dangerous. Switchgears are the key equipment in the distribution power network. In this paper, by using artificial defect models in the laboratory, partial discharge test experiments based on transient earth voltage (TEV) and acoustic emission (AE) techniques were carried out in real metal-clad switchgear. Three kinds of typical types of defect models, needle-plane discharge, internal cavity discharge and dielectric barrier discharge, were designed and positioned in three different zones of the switchgear. When applying high voltage on those defect models, PDs will occur and be detected by TEV and AE sensors located at the surface of the switchboard. Based on the recorded signals, the PD characteristics of defect models were investigated. The influence of applied voltage amplitude and defect model geometry such as the size of internal cavity on the PD activity was studied. The measurement results show that the discharge phase distributions were not the same, needle-plane discharge occurred around 135° and 315°, internal cavity discharge distributed in 90°~180° and 270°~360° when under lower voltage, distributed in 60°~160° and 260°~350° when under higher voltage. Compared with TEV method, AE techniques is more suitable for detecting dielectric barrier discharge.