Effects of Stator Winding Configurations on Steady-state Currents Characteristics of Synchronous Generator With Inter-turn Short Circuits of Field Windings

王祥珩,邱阿瑞,郝亮亮,孙宇光
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2011.30.009
2011-01-01
Abstract:In order to find out the effects of stator winding configurations on steady-state currents characteristics of field windings under inter-turn short circuits in synchronous generator,stator windings connections of a 12 kW synchronous generator with six poles were changed for several different configurations to calculate the same fault based on the multi-loop method which had been verified by experiments,then through FFT analysis the steady-state currents characteristics were achieved and on which a comparative analysis was done.Both the calculation and analysis results indicate that,in the fault of inter-turn short circuits of field windings,the steady-state harmonic characteristics of stator and rotor currents are different from other faults such as stator internal short-circuits and external short-circuits in the terminal of synchronous machine,besides,different stator winding configurations lead to different characteristics.The inter-turn short circuits fault monitoring and protection of the field windings should be on the basis of scientific fault calculation,which means machines of different types should all be analyzed and calculated specifically,and then characteristics quantity should be chosen in terms of actual situations of the machine.
What problem does this paper attempt to address?