Fault Location and Short Circuit Turns Estimation of Inter-turn Short Circuits of Field Windings in Non-salient-pole Synchronous Generator

邱阿瑞,孙宇光,王祥珩,郝亮亮
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2011.21.013
2011-01-01
Abstract:In order to realize the on-line detection and protection of the field winding inter-turn short circuit faults in synchronous generator, in this paper, the field winding inter-turn short circuit faults of a 12kW non-salient-pole synchronous generator with three pairs on load were calculated by the multi-loop method, the result of which was analyzed comparatively with the corresponding experiment. The influences of distributed field winding fault position and short circuit turns to the fault characteristic quantities were respectively discussed. On the basis, a new method of fault slots judgment anti short circuit turns estimation based on stator branch harmonic current was proposed. This paper firstly made a deep and systematical analysis to the fault law of distributed field winding inter-turn short circuit, laying a foundation for the inter-turn short circuit fault on-line detection and protection of the field windings in non-salient-pole generator.