The breakdown voltage of power transformer insulation paper after thermal aging

Chao Tang,Ruijin Liao,Feilong Huang,Lijun Yang,Mengzhao Zhu
DOI: https://doi.org/10.19595/j.cnki.1000-6753.tces.2010.11.001
2010-01-01
Abstract:Breakdown voltage is a very important dielectric parameter for dielectric materials. The analysis of breakdown voltage during aging process of transformer insulation paper is of great significance for the mechanism research. Therefore, in this paper, a set of accelerate thermal aging experiments are designed under three different temperatures (90℃、110℃、130℃) and lasted for more than 500 days, and there are two oil-paper insulation systems made up with mineral oil/thermal upgraded insulation paper, and BIOTEMP oil/thermal upgraded insulation paper used in this experiment. The test specimens were sampled periodically and then the breakdown voltages were analyzed. Further more, the main reason of the breakdown value variation was discussed. The test results indicates that, under three different temperatures, the breakdown voltage of insulation paper in both the two insulation systems had the tendency of small increase, especially under 110℃ and 90℃. The breakdown voltage of KR is entirely higher than PR. There are no obviously relations between breakdown voltage and aging temperature, neither with DP of insulation paper. During thermal aging, water in oil-paper insulation is not equilibrium, water inside insulation paper is always below 2% and the affection to breakdown voltage made by water content is very tiny. Thus, to research the whole electric performance of oil-paper insulation in future, more attention should be paid to the overall oil-paper insulation system.
What problem does this paper attempt to address?