The Effect of Aging on Electrical Lifetime of Oil Immersed Pressboard under Partial Discharge

Yanjie Cui,Shengchang Ji,Fan Zhang,Pei Cao,Lingyu Zhu,Xiaobo Ou
DOI: https://doi.org/10.1109/ipmhvc.2016.8012854
2016-01-01
Abstract:Insulation paper immersed with transformer oil is used as an electrical insulation medium in transformer for its high breakdown field strength. In the normal operation state of higher voltage power transformers, the defects in insulation medium can cause partial discharge(PD). PD is harmful for insulation materials, and shortens their life. PD activities are related with the applied voltage, which therefore decides the life being shortened. In this paper, the average electrical life of oil immersed paper under different AC voltage is studied. The PD tests were performed on a specimen of oil-immersed paper placed between the needle- to-plane electrodes. Feature parameters of PD are acquired by PDCheck and the discharge pulse waveforms are recorded by an oscilloscope. The duration of specimen under AC voltage is considered to be its electrical life. Relationship between average electrical life and applied voltage is analyzed and fitted. Test results indicated the life of insulation paper tended to decrease exponentially with increase in applied voltage, and there is a threshold voltage to the electrical aging of insulation material.
What problem does this paper attempt to address?