EXPERIMENTAL AND ANALYTICAL COMPARISON ON REGENERATING CAPABILITY OF TWO KINDS OF DEHUMIDIFYING SOLUTION

易晓勤,刘晓华,江亿,冯宁,许锋
DOI: https://doi.org/10.19912/j.0254-0096.2010.02.006
2010-01-01
Abstract:The regenerating capability of LiBr and LiCl solution was compared in the paper. A series of familiar working conditions in regenerator adopting LiBr and LiCl solutions separately were tested. Experience formulas of regenerating mass per second which was guideline to evaluate heat and mass transfer performance were educed according to experience data. The difference of regenerating mass per second between LiBr and LiCl solution is small in equal condition. In lower concentration (LiBr is 40%-43%), LiCl solution has higher regenerating mass, while in higher concentration (LiBr is 48%-50%), LiBr solution has higher regenerating mass per second.
What problem does this paper attempt to address?