RESEARCH ON THE FIELD UNIFORMITY PRINCIPLE IN LIQUID DESICCANT DEHUMIDIFIER/REGENERATOR

Liu Xiaohua,Yi Xiaoqin,Chang Xiaomin,Jiang Yi
DOI: https://doi.org/10.3321/j.issn:0254-0096.2009.07.017
2009-01-01
Abstract:Based on the analysis on the combined heat transfer process and the mass transfer process within the dehumiditier /regenerator,one finds that the changing trend of the mass transfer driving force(moisture difference) may be different with the combined heat and mass transfer driving force(enthalpy difference).The more uniform mass transfer driving force within the dehumiditier/regenerator,the better would be the mass transfer performance.In dehumidifier and hot desiccant driven regenerator,where the mass transfer direction is the same with the total heat transfer direction,counterflow configuration has the best mass transfer performance,and parallel-flow is the poorest.In the hot air driven regenerator, where the mass transfer direction is opposite to the total heat transfer direction,parallel-flow configuration performances best mass transfer performance,and counter-flow is the poorest.
What problem does this paper attempt to address?